Surge Protection Devices

Electrical networks can always transfer high voltage surges from the point of occurrence to distant locations. Lightning strikes , high voltage switching and inductive loads switching on the network, are the main sources of these traveling waves. Moreover, these surges can penetrate into the structure through direct lightning or electromagnetic induction , or even through the network of power service, electronic, telecommunications network or metal piping.
Surges, because of their nature of the source of production, are very transient . But considering that they can have high peaks of voltage amplitudes, equipments and devices connected to the network are very susceptible to serious damages. Traveling from the point of occurrence, surges can quickly reach to the end user points in the network.

According to IEC 61643 Standard, lightning protection in a structure is complemented by installing a secondary or internal protection system. In this system, a series of protective equipments or Surge Protection Devices (called SPD), are used to protect internal networks and equipments against lightning impacts. The system is designed to completely damp temporary surge currents and voltages in three levels, and it uses three types of SPDs accordingly. For instance, in a power supplying network in a building, these levels can be classified into main entrance, secondary branches and end-user points.

The SPD operation is so that in the event of surges, the protected network is connected to ground in a very short time (a few microseconds), and after the transient situation is passed, it backs to normal operation condition.

 

  • Surge Protection Devices:

 

absorber MCD

 

  • Absorber MCD

Protection against transitory surges of electrical facilities connected to single-phase low voltage 230V mains power.

Protector Type III (Fine protection).

Suitable for protection of equipment intended to be connected to an electrical installation (Category I, according to ITC-BT-23).

Technical specifications:

Nominal Voltage: UN=230V AC (50Hz)
Maximum working Voltage: UC=275V AC (50Hz)
Nominal discharge Intensity: In(8/20 μs)=5kA
Maximum discharge Intensity: Imax(8/20 μs)=8kA
Response time: tA<25 ns
Protection level: UP≤1kV

Technical sheet (PDF)


 

absorber MCD-E

  • Absorber MCD-E

Protection against transitory surges of general electrical facilities connected to single-phase low voltage 230V mains power.

Protector Type III (Fine protection).

Includes a front jack for connecting equipment to the electrical grid.

Suitable for protection of equipment intended to be connected to an electrical installation (Category I, according to ITC-BT-23).

Technical specifications:

Nominal Voltage: UN=230V AC (50Hz)
Maximum working Voltage: UC=275V AC (50Hz)
Nominal discharge Intensity: In(8/20 μs)=5kA
Maximum discharge Intensity: Imax(8/20 μs)=8kA
Response time: tA<25 ns
Protection level: UP≤1kV
Nominal load current: IL=16 A

Technical sheet (PDF)

 